FLEET #851
STARTING PROCEDURE
- POSITION GENERATOR ON LEVEL SURFACE AND ALWAYS STRICTLY OBSERVE ALL SAFETY INSTRUCTIONS.
- BEFORE STARTING, CHECK ENGINE OIL & COOLANT LEVELS.
- CHECK THAT BOTH EMERGENCY STOP BUTTONS ARE IN THE “OUT” POSITION
- CHECK THAT THE LOAD IS SWITCHED OFF.
- SWITCH KEY RUN POSITION
- CHECK WARNING LAMPS ON PCC PANEL ARE OUT
- RUN ENGINE FOR APPROXIMATELY 5 MINUTES TO WARM UP THEN PRESS BREAKER CLOSE BUTTON ON PCC PANEL TO CLOSE CIRCUIT BREAKER.
- CHECK AC VOLTMETER AND FREQUENCY METER.
- SWITCH ON THE LOAD AND CHECK THE KILOWATT METER, AC VOLTMETER AND FREQUENCY METER ALLOWING A MAXIMUM 10% IMBALANCE BETWEEN PHASES RECOMMENDED.
SHUTDOWN
- SITCH OFF THE LOAD.
- PRESS BREAKER ON BUTTON
- LET ENGINE RUN FOR APPROXIMATELY 5 MINUTES
- SWITCH KEY SWITCH TO OFF.