FLEET #851

STARTING PROCEDURE

  1. POSITION GENERATOR ON LEVEL SURFACE AND ALWAYS STRICTLY OBSERVE ALL SAFETY INSTRUCTIONS.
  2. BEFORE STARTING, CHECK ENGINE OIL & COOLANT LEVELS.
  3. CHECK THAT BOTH EMERGENCY STOP BUTTONS ARE IN THE “OUT” POSITION
  4. CHECK THAT THE LOAD IS SWITCHED OFF.
  5. SWITCH KEY RUN POSITION
  6. CHECK WARNING LAMPS ON PCC PANEL ARE OUT
  7. RUN ENGINE FOR APPROXIMATELY 5 MINUTES TO WARM UP THEN PRESS BREAKER CLOSE BUTTON ON PCC PANEL TO CLOSE CIRCUIT BREAKER.
  8. CHECK AC VOLTMETER AND FREQUENCY METER.
  9. SWITCH ON THE LOAD AND CHECK THE KILOWATT METER, AC VOLTMETER AND FREQUENCY METER ALLOWING A MAXIMUM 10% IMBALANCE BETWEEN PHASES RECOMMENDED.

SHUTDOWN

  1. SITCH OFF THE LOAD.
  2. PRESS BREAKER ON BUTTON
  3. LET ENGINE RUN FOR APPROXIMATELY 5 MINUTES
  4. SWITCH KEY SWITCH TO OFF.