FLEET #554
STARTING PROCEDURE
- POSITION GENERATOR ON LEVEL SURFACE AND ALWAYS STRICTLY OBSERVE ALL SAFETY INSTRUCTIONS.
- BEFORE STARTING, CHECK ENGINE OIL & COOLANT LEVELS.
- CHECK CIRCUIT BREAKER Q1 IS SWITCHED OFF (OR OPEN).
- CHECK EMERGENCY STOP IS IN “OUT” POSITION.
- CHECK THAT THE LOAD IS SWITCHED OFF.
- CHECK THAT THE EARTH FAULT PROTECTION HAS NOT TRIPPED (RESET IF NECESSARY).
- PUT STARTER SWITCH IN POSITION 1. PUSH DOWN THE STARTER SWITCH INTO LOWEST POSITION AND RELEASE IT AS SOON AS THE NEGINE FIRES. THE SWITCH AUTOMATICALLY RETURNS TO POSITION 1.
- CHECK THE WARNING LAMPS ON CONTROL PANEL AND INDICATOR PANELS: ARE OUT.
- RUN ENGINE FOR 5 MINUTES APPROXIMATELY TO WARM UP THEN CHECK ENGINE OIL PRESSURE AND COOLING WATER TEMPERATURE.
- CHECK VOLTMETER AND FREQUENCY METER.
- SWITCH CIRCUIT BREAKER Q1 ON BY PUSHING THE LEVER FULLY DOWN FROM TRIPPED (WHITE) TO OFF (GREEN) FOLLOWED BY PUSHING THE LEVER FULLY UP TO ON (RED).
- SWITCH ON THE LOAD AND CHECK THE AMMETERS, VOLTMETER AND FREQUENCY METER ALLOWING A MAXIMUM 10% IMBALANCE BETWEEN PHASES RECOMMENDED.
SHUTDOWN
- SITCH OFF THE LOAD.
- SWITCH OFF CIRCUIT BREAKER Q1.
- LET ENGINE RUN FOR ABOUT 5 MINUTES
- STOP THE ENGINE BY PUTTING THE STARTER SWITCH IN POSITION O.